Parameters
List of parameters
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
Dependency:
Refer to: r2050
Notice:
Where there is a multiple interconnection of a connector output, all the connector inputs must either have Integer or
FloatingPoint data types.
A BICO interconnection for a single PZD can only take place either on r2050 or r2060.
p2061[0...12]
CI: PROFIBUS PZD send double word / PZD send DW
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Selects the PZD (actual values) with double word format to be sent to the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
Dependency:
Refer to: p2051
Notice:
A BICO interconnection for a single PZD can only take place either on p2051 or p2061.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
r2063[0...12]
PROFIdrive diagnostics PZD send double word / Diag send DW
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the PZD (actual values) with double word format sent to the fieldbus controller.
Index:
[0] = PZD 1 + 2
[1] = PZD 2 + 3
[2] = PZD 3 + 4
[3] = PZD 4 + 5
[4] = PZD 5 + 6
[5] = PZD 6 + 7
[6] = PZD 7 + 8
[7] = PZD 8 + 9
[8] = PZD 9 + 10
[9] = PZD 10 + 11
[10] = PZD 11 + 12
[11] = PZD 12 + 13
[12] = PZD 13 + 14
Bit field:
Bit
Signal name
00
Bit 0
01
Bit 1
1-260
Calculated: -
Scaling: 4000H
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
ON
ON
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: U32 / Integer32
Dyn. index: -
Func. diagram: 2470
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2450, 2470
Factory setting
-
0 signal
OFF
OFF