Parameters
List of parameters
Note:
The identification of "fixed stop outside the monitoring window" is, for the factory setting, dependent on signal BO:
r2526.5 (fixed stop outside window). This signal is influenced via p2635 (EPOS fixed stop monitoring window).
p2639
BI: EPOS torque limit reached / M_limit reached
CU250D-2_DP_F
Access level: 3
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the feedback signal "torque limit reached" when traversing to fixed stop.
BI: p2639 = 1 signal
Torque limit is reached.
BI: p2639 = 0 signal
Torque limit is not reached.
Dependency:
Refer to: r1407
Note:
The feedback signal from "torque limit reached" is, for the factory setting, dependent on the signal BO: r1407.7
(torque limit reached).
p2640
BI: EPOS intermediate stop (0 signal) / Intermediate stop
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the "no intermediate stop/intermediate stop".
BI: p2640 = 1 signal
No intermediate stop.
BI: p2640 = 0 signal
Intermediate stop.
Dependency:
Refer to: p2631, p2641, p2647, p2649
Caution:
For BI: p2649 = 1 signal, the following applies:
Motion starts without any explicit control signal.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
This signal is only effective in the modes "traversing blocks" and "direct setpoint input/MDI".
When activating the intermediate stop, the axis brakes with the parameterized deceleration (p2620 or p2645).
p2641
BI: EPOS reject traversing task (0 signal) / Trav_task reject
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for "do not reject traversing task/reject traversing task".
BI: p2641 = 1 signal
Do not reject traversing task.
BI: p2641 = 0 signal
Reject traversing task.
Dependency:
Refer to: p2631, p2640, p2647, p2649
Caution:
For BI: p2649 = 1 signal, the following applies:
Motion starts without any explicit control signal.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
1-354
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3616
Factory setting
1407.7
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3616, 3620, 3625
Factory setting
0
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3616, 3620, 3625
Factory setting
0