Download Print this page

Siemens SINAMICS G120D List Manual page 35

Hide thumbs Also See for SINAMICS G120D:

Advertisement

13
Alarm motor overtemperature
14
Motor rotates forwards
15
Alarm drive converter overload
Caution:
p2080 is used to define the signal sources of the PROFIdrive status word interconnection.
Note:
Re bit 03:
This signal is inverted if it is interconnected to a digital output.
Re r0052:
The status bits have the following sources:
Bit 00: r0899 Bit 0
Bit 01: r0899 Bit 1
Bit 02: r0899 Bit 2
Bit 03: r2139 Bit 3 (or r1214.10 for p1210 > 0)
Bit 04: r0899 Bit 4
Bit 05: r0899 Bit 5
Bit 06: r0899 Bit 6
Bit 07: r2139 Bit 7
Bit 08: r2197 Bit 7
Bit 09: r0899 Bit 7
Bit 10: r2197 Bit 6
Bit 11: r0056 Bit 13 (negated)
Bit 12: r0899 Bit 12
Bit 13: r2135 Bit 14 (negated)
Bit 14: r2197 Bit 3
Bit 15: r2135 Bit 15 (negated)
r0053.0...11
CO/BO: Status word 2 / ZSW 2
Access level: 2
Can be changed: -
Units group: -
Min
-
Description:
Display and BICO output for status word 2.
Bit field:
Bit
Signal name
00
DC braking active
01
|n_act| > p1226 (n_standstill)
02
|n_act| > p1080 (n_min)
03
I_act >= p2170
04
|n_act| > p2155
05
|n_act| <= p2155
06
|n_act| >= r1119 (n_set)
07
Vdc <= p2172
08
Vdc > p2172
09
Ramp-up/ramp-down completed
10
Technology controller output at the lower
limit
11
Technology controller output at the upper
limit
Caution:
p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note:
The following status bits are displayed in r0053:
Bit 00: r1239 Bit 8
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
No
Yes
No
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of parameters
Yes
No
Yes
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
-
-
-
FP
-
-
-
-
-
-
-
-
-
-
-
-
1-35

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all