Download Print this page

Siemens SINAMICS G120D List Manual page 415

Hide thumbs Also See for SINAMICS G120D:

Advertisement

p9484
BICO interconnections search signal source / BICO S_src srch
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the signal source (BO/CO parameter, BICO coded) to search in the signal sinks.
The signal source to be searched for is set in p9484 (BICO-coded) and the search result is specified using the num-
ber (r9485) and the first index (r9486).
Dependency:
Refer to: r9485, r9486
r9485
BICO interconnections signal source search count / BICO S_src srchQty
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the number of BICO interconnections to the signal sink being searched for.
Dependency:
Refer to: p9484, r9486
Note:
The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
r9486
BICO interconnections signal source search first index / BICO S_src srchIdx
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the first index of the signal source being searched for.
The signal source to be searched for is set in p9484 (BICO-coded) and the search result is specified using the num-
ber (r9485) and the first index (r9486).
Dependency:
Refer to: p9484, r9485
Note:
The signal source to be searched is set in p9484 (BICO-coded).
The search result is contained in r9482 and r9483 and is specified by the count (r9485) and the first index (r9486).
p9501
SI Motion enable safety functions (Control Unit) / SI Mtn enable CU
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
-
Description:
Sets the enable signals for the safe motion monitoring.
Bit field:
Bit
Signal name
00
Enable SI Motion
16
Enable SSM (n < nx) hysteresis and filtering Enable
17
Enable SDI
30
Enable F-DI in PROFIsafe telegram
Dependency:
Refer to: F01682, F01683
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Enable
Enable
Enable
Parameters
List of parameters
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0000 0000 0000 0000 0000 0000
0000 0000 bin
0 signal
Inhibit
Inhibit
Inhibit
Inhibit
FP
-
2823
2824
-
1-415

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all