A07463 (F)
EPOS: External block change not requested in the traversing block
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a traversing block with the block change enable CONTINUE_EXTERNAL_ALARM, the external block change
was not requested.
Alarm value (r2124, interpret decimal):
Number of the traversing block.
Remedy:
Resolve the reason as to why the edge is missing at binector input (BI: p2632).
F07464
EPOS: Traversing block is inconsistent
Reaction:
OFF1 (OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
The traversing block does not contain valid information.
Alarm value (r2124, interpret decimal):
Number of the traversing block with invalid information.
Remedy:
Check the traversing block and where relevant, take into consideration alarms that are present.
A07465
EPOS: Traversing block does not have a subsequent block
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no subsequent block in the traversing block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with the missing subsequent block.
Remedy:
- parameterize this traversing block with the block change enable END.
- parameterize additional traversing blocks with a higher block number and for the last block, using the block change
enable END.
A07466
EPOS: Traversing block number assigned a multiple number of times
Reaction:
NONE
Acknowledge:
NONE
Cause:
The same traversing block number was assigned a multiple number of times.
Alarm value (r2124, interpret decimal):
Number of the traversing block that was assigned a multiple number of times.
Remedy:
Correct the traversing blocks.
A07467
EPOS: Traversing block has illegal task parameters
Reaction:
NONE
Acknowledge:
NONE
Cause:
The task parameter in the traversing block contains an illegal value.
Alarm value (r2124, interpret decimal):
Number of the traversing block with an illegal task parameter.
Remedy:
Correct the task parameter in the traversing block.
A07468
EPOS: Traversing block jump destination does not exist
Reaction:
NONE
Acknowledge:
NONE
Cause:
In a traversing block, a jump was programmed to a non-existent block.
Alarm value (r2124, interpret decimal):
Number of the traversing block with a jump destination that does not exist.
Remedy:
- correct the traversing block.
- add the missing traversing block.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Faults and alarms
List of faults and alarms
3-827