F01660
SI P1: Safety-related functions not supported
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The Power Module does not support the safety-related functions. Safety Integrated cannot be commissioned.
Note:
This fault does not result in a safety stop response.
Remedy:
- use a Power Module that supports the safety-related functions.
F01661
SI P1: Simulation of the safety inputs active
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The simulation of the digital inputs of the Control Unit (p0795) is active.
It is not permissible that safety inputs are simulated.
Fault value (r0949, interpret binary):
The displayed bits indicate which digital inputs must not be simulated.
Remedy:
- Deactivate the simulation of the digital inputs of the Control Unit for the safety inputs (p0795).
- acknowledge fault.
F01662
Error internal communications
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
A module-internal communication error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
F01663
SI P1: Copying the SI parameters rejected
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
One of the following values is saved in p9700 or was entered offline: 87 or 208.
This is the reason that when booting, an attempt is made to copy SI parameters from processor 1 to processor 2.
However, no safety-relevant function has been selected on processor 1 (p9501 = 0, p9601 = 0). This is the reason
that copying is not possible.
Note:
This fault does not result in a safety stop response.
See also: p9700 (SI copy function)
Remedy:
- Set p9700 to 0.
- Check p9501 and/or p9601 and if required, correct.
- Restart the copying function by entering the corresponding value into p9700.
F01665
SI P1: System is defective
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A system defect was detected before the last boot or in the actual one. The system might have been rebooted (reset).
Fault value (r0949, interpret hexadecimal):
200000 hex, 400000 hex, 8000yy hex (yy any):
- Fault in the actual booting/operation.
Additional values:
- defect before the last time that the system booted.
Remedy:
- carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
Re fault value = 200000 hex, 400000 hex, 8000yy hex (yy any):
- ensure that the Control Unit is connected to the Power Module.