Faults and alarms
List of faults and alarms
Re alarm value = 502:
Check the enable of F-DI (p9501.30).
A08526 (F)
PROFINET: No cyclic connection
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no connection to a PROFINET controller.
Remedy:
Establish the cyclic connection and activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000, r61001).
A08565
PROFINET: Consistency error affecting adjustable parameters
Reaction:
NONE
Acknowledge:
NONE
Cause:
A consistency error was detected when activating the configuration (p8925 = 1) for the PROFINET interface. The
currently set configuration has not been activated.
Possible causes:
- IP address, subnet mask or default gateway is not correct
- IP address or station name used twice in the network
- station name contains invalid characters, etc.
See also: p8920 (PN Name of Station), p8921 (PN IP address of station), p8922 (PN Default Gateway of Station),
p8923 (PN Subnet Mask of Station)
Remedy:
Check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925 = 1).
See also: p8925 (PN interface configuration)
A08760
CAN: maximum size of the PZD IF exceeded
Reaction:
NONE
Acknowledge:
NONE
Cause:
The maximum size of the PZD interface exceeded.
Fault value 1: receiving
Fault value 2: sending
Deleting the alarm:
- Power Off/On
- Warm restart
- CANopen NMT state change
- reset alarm with p2111
Remedy:
Map fewer process data in PDO.
A08800
PROFIenergy energy-saving mode active
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PROFIenergy energy-saving mode is active
Alarm value (r2124, interpret decimal):
Mode ID of the active PROFIenergy energy-saving mode.
See also: r5600 (Pe energy saving mode ID)
Remedy:
The alarm automatically disappears when the energy-saving mode is exited.
Note:
After receiving the PROFIenergy command "End_Pause" via PROFINET, the energy-saving mode is exited.
A08802
PROFIenergy not possible to switch off incremental encoder supply
Reaction:
NONE
Acknowledge:
NONE
Cause:
The incremental encoder is used for the closed-loop position control. This means that its power supply cannot be
switched off during the PROFIenergy energy-saving mode, otherwise it would lose its position actual value.
Alarm value (r2124, interpret decimal):
Encoder number
Remedy:
The alarm automatically disappears when the energy-saving mode is exited.
Note:
After receiving the PROFIenergy command "End_Pause" via PROFINET, the energy-saving mode is exited.
3-852
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013