Parameters
List of parameters
r2250
CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: 9_1
CU240D-2_PN_F
Min
- [%]
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
Refer to: r2245
p2251
Technology controller mode / Tec_ctrl mode
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Sets the mode for using the technology controller output.
Value:
0:
1:
Dependency:
p2251 = 0, 1 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
p2253[0...n]
CI: Technology controller setpoint 1 / Tec_ctrl setp 1
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2254, p2255
p2254[0...n]
CI: Technology controller setpoint 2 / Tec_ctrl setp 2
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2253, p2256
1-306
Technology controller as main speed setpoint
Technology controller as supplementary speed setpoint
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7954
Factory setting
- [%]
Data type: Integer16
Dyn. index: -
Func. diagram: 7958
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 7958
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 7958
Factory setting
0