p0760[0...1]
CU analog inputs characteristic value y2 / CU AI char y2
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-1000.00 [%]
Description:
Sets the scaling characteristic for the analog inputs.
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
The parameters for the characteristic do not have a limiting effect.
p0761[0...1]
CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.00
Description:
Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency:
For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
Refer to: p0756
Note:
AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
p0762[0...1]
CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0 [ms]
Description:
Sets the delay time for the wire breakage monitoring of the analog inputs.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Note:
AI: Analog Input
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
20.00
Calculated: -
Scaling: -
Unit selection: -
Max
1000 [ms]
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9566, 9568, 9576
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 9566, 9568
Factory setting
2.00
Data type: Unsigned16
Dyn. index: -
Func. diagram: 9566, 9568
Factory setting
100 [ms]