Parameters
List of parameters
p0797[0...1]
CU analog inputs simulation mode / CU AI sim_mode
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the simulation mode for the analog inputs.
Value:
0:
1:
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency:
The setpoint for the input voltage is specified via p0798.
Refer to: p0798
Note:
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
p0798[0...1]
CU analog inputs simulation mode setpoint / CU AI sim setp
Access level: 3
Can be changed: U, T
Units group: -
Min
-50.000
Description:
Sets the setpoint for the input value in the simulation mode of the analog inputs.
Index:
[0] = AI0 (X10.3)
[1] = AI1 (X10.4)
Dependency:
The simulation of an analog input is selected using p0797.
If AI x is parameterized as a voltage input (p0756), the setpoint is a voltage in V.
Refer to: p0756, p0797
Note:
This parameter is not saved when data is backed up (p0971).
AI: Analog Input
p0802
Data transfer: memory card as source/target / mem_card src/targ
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the number for data transfer of a parameter backup from/to memory card.
Transfer from memory card to device memory (p0804 = 1):
- Sets the source of parameter backup (e.g. p0802 = 48 --> PS048xxx.ACX is the source).
Transfer from non-volatile device memory to memory card (p0804 = 2):
- Sets the target of parameter backup (e.g. p0802 = 23 --> PS023xxx.ACX is the target).
Dependency:
Refer to: p0803, p0804
Notice:
If the data between the volatile and non-volatile device memories differ, then it may be necessary to save the data
on the memory card in a non-volatile fashion prior to the transfer (e.g. p0971 = 1).
1-118
Terminal evaluation for analog input x
Simulation for analog input x
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
2000.000
Calculated: -
Scaling: -
Unit selection: -
Max
100
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.000
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0