p1088[0...n]
CI: Speed limit in negative direction of rotation / n_limit neg
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the speed/velocity limit of the negative direction.
p1091[0...n]
Skip speed 1 / n_skip 1
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets skip speed 1.
Dependency:
Refer to: p1092, p1093, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Note:
The skip (suppression) speeds can be used to prevent the effects of mechanical resonance.
p1092[0...n]
Skip speed 2 / n_skip 2
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets skip speed 2.
Dependency:
Refer to: p1091, p1093, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1093[0...n]
Skip speed 3 / n_skip 3
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets skip speed 3.
Dependency:
Refer to: p1091, p1092, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
p1094[0...n]
Skip speed 4 / n_skip 4
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets skip speed 4.
Dependency:
Refer to: p1091, p1092, p1093, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
1-160
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
210000.000 [rpm]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3050
Factory setting
1086[0]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3050
Factory setting
0.000 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3050
Factory setting
0.000 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3050
Factory setting
0.000 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3050
Factory setting
0.000 [rpm]