Download Print this page

Siemens SINAMICS G120D List Manual page 162

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Parameters
List of parameters
Dependency:
Refer to: p1080
Notice:
The effective minimum speed is formed from p1080 and p1106.
p1108[0...n]
BI: Total setpoint selection / Total setp sel
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to select the total setpoint.
Dependency:
The selection of the total speed setpoint is automatically interconnected to the status word of the technology con-
troller (r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
Refer to: p1109
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to withdraw the inter-
connection to its status word (r2349.4).
p1109[0...n]
CI: Total setpoint / Total setp
Access level: 4
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency:
The signal source of the total setpoint is automatically interconnected to the output of the technology controller
(r2294) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
Refer to: p1108
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the inter-
connection to its output (r2294).
p1110[0...n]
BI: Inhibit negative direction / Inhib neg dir
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to disable the negative direction.
Dependency:
Refer to: p1111
p1111[0...n]
BI: Inhibit positive direction / Inhib pos dir
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to disable the positive direction.
Dependency:
Refer to: p1110
1-162
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 3030
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3030
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2505, 3040
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2505, 3040
Factory setting
0

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all