Remedy:
- check whether the connected encoder type matches the encoder that has been parameterized.
- correct the parameter specified by the fault value (r0949) and p0187.
- re parameter number = 314:
- check the pole pair number and measuring gear ratio. The quotient of the "pole pair number" divided by the "mea-
suring gear ratio" must be less than or equal to 1000 ((r0313 * p0433) / p0432 <= 1000).
A31915 (F, N)
Encoder 1: Configuration error
Reaction:
NONE
Acknowledge:
NONE
Cause:
The configuration for encoder 1 is incorrect.
Alarm value (r2124, interpret decimal):
1:
Re-parameterization between fault/alarm is not permissible.
419:
When the fine resolution Gx_XIST2 is configured, the encoder identifies a maximum possible absolute position
actual value (r0483) that can no longer be represented within 32 bits.
Remedy:
Re alarm value = 1:
No re-parameterization between fault/alarm.
Re alarm value = 419:
Reduce the fine resolution (p0419) or deactivate the monitoring (p0437.25), if the complete multiturn range is not
required.
A31930 (N)
Encoder 1: Data logger has saved data
Reaction:
NONE
Acknowledge:
NONE
Cause:
For the activated function "Data logger" (p0437.0 = 1) a fault has occurred with the Sensor Module. This alarm indi-
cates that the diagnostics data corresponding to the fault was saved on the memory card.
The diagnostics data is saved in the following folder:
/USER/SINAMICS/DATA/SMTRC00.BIN
...
/USER/SINAMICS/DATA/SMTRC07.BIN
/USER/SINAMICS/DATA/SMTRCIDX.TXT
The following information is contained in the TXT file:
- Display of the last written BIN file.
- Number of write operations that are still possible (from 10000 downwards).
Note:
Only Siemens can evaluate the BIN files.
Remedy:
Not necessary.
The alarm disappears automatically.
The data logger is ready to record the next fault case.
F31950
Encoder 1: Internal software error
Reaction:
ENCODER (OFF2)
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
The fault value contains information regarding the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- If necessary, upgrade the firmware in the Sensor Module to a later version.
- contact the Hotline.
A31999 (F, N)
Encoder 1: Unknown alarm
Reaction:
NONE
Acknowledge:
NONE
Cause:
A alarm has occurred on the Sensor Module for encoder 1 that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Faults and alarms
List of faults and alarms
3-881

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all