Siemens SINAMICS G120D List Manual page 12

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Parameters
Overview of parameters
Calculated
Specifies whether the parameter is influenced by automatic calculations.
p0340 determines which calculations are to be performed:
• p0340 = 1 includes the calculations from p0340 = 2, 3, 4, 5.
• p0340 = 2 calculates the motor parameters (p0350 ... p0360, p0625).
• p0340 = 3 includes the calculations from p0340 = 4, 5.
• p0340 = 4 only calculates the controller parameters.
• p0340 = 5 only calculates the controller limits.
Note:
For p3900 > 0, p0340 = 1 is also called automatically.
After p1900 = 1, 2, p0340 = 3 is also called automatically.
Parameters with a reference to p0340 after "Calculated", depend on the Power
Module being used and the motor. In this case, the values at "Factory setting" do
not correspond to the actual values because these values are calculated during
the commissioning. This also applies to the motor parameters.
Data type
The information on the data type can consist of the following two items (separated
by a slash):
• First item
Data type of the parameter.
• Second item (for binector or connector input only)
Data type of the signal source to be interconnected (binector/connector out-
put).
Parameters can have the following data types:
• Integer8
• Integer16
• Integer32
• Unsigned8
• Unsigned16
• Unsigned32
• FloatingPoint32
Depending on the data type of the BICO input parameter (signal sink) and BICO
output parameter (signal source), the following combinations are possible when
creating BICO interconnections:
1-12
I8
8-bit integer
I16
16-bit integer
I32
32-bit integer
U8
8 bits without sign
U16
16 bits without sign
U32
32 bits without sign
Float
32-bit floating point number
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013