Siemens SINAMICS G120D List Manual page 461

Hide thumbs Also See for SINAMICS G120D:

Advertisement

04
SLS_active
05
SDI_pos_active
06
SDI_neg_active
p10142[0...5]
SI F-DO 0 signal sources (processor 2) / SI F-DO 0 S_src P2
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
0
Description:
Sets the signal sources for F-DO 0 (X131.6).
The 6 signal sources in p10142[0...5] are AND'ed and the result is output at F-DO 0.
Value:
0:
1:
2:
5:
6:
7:
9:
12:
13:
Index:
[0] = AND logic operation input 1
[1] = AND logic operation input 2
[2] = AND logic operation input 3
[3] = AND logic operation input 4
[4] = AND logic operation input 5
[5] = AND logic operation input 6
Note:
F-DO: Failsafe Digital Output
p10146
SI test sensor feedback signal / SI test sens FS
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
-
Description:
Sets the test of the feedback line for forced checking procedure.
Bit field:
Bit
Signal name
00
Test F-DO 0
Note:
F-DO: Failsafe Digital Output
p10147
SI F-DO test stop mode / SI F-DO test mode
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
2
Description:
Sets the test stop mode for the safety digital output (F-DO)
Value:
2:
3:
4:
Dependency:
Refer to: p10001, p10003, p10007, p10046
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
No function
STO active
SS1 active
SLS active
SSM feedback signal active
Safe state
Internal event
SDI positive active
SDI negative active
Test mode 2 read back F-DO in DI (relay circuit)
Test mode 3 read back F-DO in DI (actuator with feedback signal)
Test mode 4 evaluation of two internal diagnostic signals
Selected
Selected
Selected
Calculated: -
Scaling: -
Unit selection: -
Max
13
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Test active
Calculated: -
Scaling: -
Unit selection: -
Max
4
Parameters
List of parameters
Not selected
Not selected
Not selected
Data type: Integer16
Dyn. index: -
Func. diagram: 2857
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: 2848
Factory setting
0000 bin
0 signal
No test
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
4
-
-
-
FP
-
1-461