Download Print this page

Siemens SINAMICS G120D List Manual page 67

Hide thumbs Also See for SINAMICS G120D:

Advertisement

p0350[0...n]
Motor stator resistance cold / Mot R_stator cold
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0.00000 [ohm]
Description:
Sets the stator resistance of the motor at ambient temperature p0625 (phase value).
Dependency:
Refer to: p0625, r1912
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The motor identification routine determines the stator resistance from the total stator resistance minus the cable
resistance (p0352).
p0352[0...n]
Cable resistance / R_cable
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0.00000 [ohm]
Description:
Resistance of the power cable between the power unit and motor.
Caution:
The cable resistance should be entered prior to motor data identification. If it is used subsequently, the difference
by which p0352 was changed must be subtracted from the stator resistance p0350 or motor data identification must
be repeated.
Note:
The parameter influences the temperature adaptation of the stator resistance.
The motor identification sets the cable resistance to 20% of the measured total resistance if p0352 is zero at the
time that the measurement is made. If p0352 is not zero, then the value is subtracted from the measured total stator
resistance to calculate stator resistance p0350. In this case, p0350 is a minimum of 10% of the measured value.
The cable resistance is reset when quick commissioning is exited with p3900 > 0.
If the stator resistance is available in a motor list, and if p0352 is still zero, then the cable resistance is generated
from the difference between the measured value and list value.
p0354[0...n]
Motor rotor resistance cold / Mot R_r cold
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0.00000 [ohm]
Description:
Sets the rotor/secondary section resistance of the motor at the ambient temperature p0625.
This parameter value is automatically calculated using the motor model (p0340 = 1, 2) or using the motor data iden-
tification routine (p1910).
Dependency:
Refer to: p0625
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The parameter is not used for synchronous motors (p0300 = 2).
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: p0340 = 1,2
Scaling: -
Unit selection: -
Max
2000.00000 [ohm]
Calculated: -
Scaling: -
Unit selection: -
Max
120.00000 [ohm]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: -
Max
300.00000 [ohm]
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00000 [ohm]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00000 [ohm]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 6727
Factory setting
0.00000 [ohm]
1-67

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all