p2579
CI: EPOS software limit switch plus signal source / SW limSwPlus S_src
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the software limit switch plus.
Dependency:
Refer to: p2578, p2580, p2581, p2582
Refer to: A07470, A07478, A07480, F07482
Notice:
A change to the software limit switch becomes immediately effective.
If the software limit switch is changed, then this results in the positions in the traversing blocks being checked.
Note:
The following applies for the setting of the software limit switch:
Software limit switch minus < software limit switch plus
p2580
CO: EPOS software limit switch minus / SW limSwitch minus
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: U, T
Units group: -
Min
-2147482648 [LU]
Description:
Sets the software limit switch in the negative direction of travel.
Dependency:
Refer to: p2578, p2579, p2581, p2582
p2581
CO: EPOS software limit switch plus / SW lim switch plus
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: U, T
Units group: -
Min
-2147482648 [LU]
Description:
Sets the software limit switch in the positive direction of travel.
Dependency:
Refer to: p2578, p2579, p2580, p2582
p2582
BI: EPOS software limit switch activation / SW lim sw act
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to activate the "software limit switch".
Dependency:
Refer to: p2578, p2579, p2580, p2581
Caution:
Software limit switch effective:
- axis is referenced (r2684.11 = 1) and BI: p2582 = 1 signal.
Software limit switch ineffective:
- modulo correction active (BI: p2577 = 1 signal).
- search for reference is executed.
Notice:
Target position for relative positioning outside software limit switch:
The traversing block is started and the axis comes to a standstill at the software limit switch. An appropriate alarm is
output and the traversing block is interrupted. Traversing blocks with valid position can be activated.
Target position for absolute positioning outside software limit switch:
In the "traversing blocks" mode, the traversing block is not started and an appropriate fault is output.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
2147482647 [LU]
Calculated: -
Scaling: -
Unit selection: -
Max
2147482647 [LU]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of parameters
Data type: U32 / Integer32
Dyn. index: -
Func. diagram: 3630
Factory setting
2581[0]
Data type: Integer32
Dyn. index: -
Func. diagram: 3630
Factory setting
-2147482648 [LU]
Data type: Integer32
Dyn. index: -
Func. diagram: 3630
Factory setting
2147482647 [LU]
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 3630
Factory setting
0