Parameters
List of parameters
13
Start count. bit 1
14
Start count. bit 2
15
Start count. bit 3
Note:
Re bit 00:
State to display the single initialization after POWER ON.
Re bit 01:
State in which the automatic restart function waits for faults (initial state).
Re bit 02:
General display that a fault has been identified and that the restart or acknowledgement has been initiated.
Re bit 03:
Displays the acknowledge command within the "acknowledge alarms" state (bit 4 = 1). For bit 5 = 1 or bit 6 = 1, the
acknowledge command is continually displayed.
Re bit 04:
State in which the faults that are present are acknowledged. The state is exited again after successful acknowl-
edgement. A change is only made into the next state if it is signaled that a fault is no longer present after an
acknowledgement command (bit 3 = 1).
Re bit 05:
State in which the drive is automatically powered up (only for p1210 = 4, 6).
Re bit 06:
State in which the system waits after having been powered up, to the end of the start attempt (to the end of the
magnetizing process).
For p1210 = 1, this signal is directly set after the faults have been successfully acknowledged.
Re bit 07:
State which is assumed after a fault occurs within the automatic restart function. This is only reset after acknowl-
edging the fault and withdrawing the power-on command.
Re bit 10:
When the automatic restart function is active, r1214.7 is displayed, otherwise the active fault r2139.3.
Re bits 12 ... 15:
Actual state of the start counter (binary coded).
Re bit 04 in addition:
For p1210 = 26, the system waits in this state until the switch-on command is available.
p1215
Motor holding brake configuration / Brake config
Access level: 2
Can be changed: T
Units group: -
Min
0
Description:
Sets the holding brake configuration.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p1216, p1217, p1226, p1227, p1228
Caution:
For the setting p1215 = 0, if a brake is used, it remains closed. If the motor moves, this will destroy the brake.
Notice:
If p1215 was set to 1 or if p1215 was set to 3, then when the pulses are suppressed, the brake is closed even if the
motor is still rotating. Pulse suppression can either be caused by a 0 signal at p0844, p0845 or p0852 or as a result
of a fault with OFF2 response. If this is not desirable (e.g. for a flying restart), then the brake can be kept open using
a 1 signal at p0855.
Note:
If a holding brake integrated in the motor is used, then it is not permissible that p1215 is set to 3.
if an external motor holding brake is being used, then p1215 should be set to 3 and r0899.12 should be intercon-
nected as control signal.
The parameter can only be set to zero when the pulses are inhibited.
1-180
No motor holding brake available
Motor holding brake acc. to sequence control
Motor holding brake always open
Motor holding brake like sequence control connection via BICO
ON
ON
ON
Calculated: -
Scaling: -
Unit selection: -
Max
3
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
OFF
OFF
OFF
Data type: Integer16
Dyn. index: -
Func. diagram: 2701
Factory setting
0
-
-
-