Motor temperature model 1:
p0605 also defines the target temperature of the model for r0034 = 100 %. Therefore, p0605 has no influence on
the time up to alarm A07012 being issued. The time is only determined by time constant p0611, the actual current
and the reference value p0305.
Note:
The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0606[0...n]
Mot_temp_mod 2/KTY timer / Mod 2/KTY t_timer
Access level: 4
Can be changed: C(3), U, T
Units group: -
Min
0.000 [s]
Description:
Sets the timer for monitoring the motor temperature for motor temperature model 2 or KTY.
This timer is started when the temperature alarm threshold (p0604) is exceeded.
If the timer has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011 is
output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer has expired, then fault F07011
is immediately output.
Dependency:
Refer to: p0604, p0605
Refer to: F07011, A07910
Note:
With p0606 = 0 s, the timer is de-activated and only the fault threshold is effective.
KTY sensor: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC sensor, bimetallic NC contact: The timer minimum value has no special significance.
p0607[0...n]
Temperature sensor fault timer / Sensor fault time
Access level: 4
Can be changed: C(3), U, T
Units group: -
Min
0.000 [s]
Description:
Sets the timer between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer is started.
If the sensor fault is still present after the timer has expired, a corresponding fault is output.
Notice:
The parameterized time is internally rounded-off to an integer multiple of 48 ms.
Note:
If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
p0610[0...n]
Motor overtemperature response / Mot temp response
Access level: 2
Can be changed: C(3), T
Units group: -
Min
0
Description:
Sets the system response when the motor temperature reaches the alarm threshold.
Value:
0:
1:
2:
12:
Dependency:
Refer to: p0601, p0604, p0605, p0614, p0615
Refer to: F07011, A07012, A07910
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
No response only alarm no reduction of I_max
Messages, reduction of I_max
Messages, no reduction of I_max
Messages, no reduction of I_max, temperature storage
Calculated: -
Scaling: -
Unit selection: -
Max
600.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
600.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
12
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8016
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.100 [s]
Data type: Integer16
Dyn. index: MDS
Func. diagram: 8016
Factory setting
12