000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4
= 1).
Bit field:
Bit
Signal name
00
Enable STO via terminals (processor 2)
03
Enable PROFIsafe (processor 2)
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change only becomes effective after a POWER ON.
STO: Safe Torque Off
p9810
SI PROFIsafe address (processor 2) / SI PROFIsafe P2
Access level: 3
Can be changed: C(95)
Units group: -
Min
0000 hex
Description:
Sets the PROFIsafe address on processor 2.
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
p9850
SI F-DI changeover tolerance time (processor 2) / SI F-DI_chg tol P2
Access level: 3
Can be changed: C(95)
Units group: -
Min
0.00 [µs]
Description:
Sets the tolerance time for the changeover of the failsafe digital input for STO on processor 2.
An F-DI changeover is not effective simultaneously due to the different runtimes in the two monitoring channels.
After an F-DI changeover, dynamic data is not subject to a crosswise data comparison during this tolerance time.
Dependency:
Refer to: p9650
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
For a crosswise data comparison between p9650 and p9850, a difference of one Safety monitoring clock cycle is
tolerated.
The parameterized time is rounded internally to an integer multiple of the monitoring clock cycle.
F-DI: Failsafe Digital Input
p9851
SI STO debounce time (processor 2) / SI STO t_debou P2
Access level: 3
Can be changed: C(95)
Units group: -
Min
0.00 [µs]
Description:
Sets the debounce time for the failsafe digital inputs used to control the "STO" function.
The debounce time is rounded to whole milliseconds.
Dependency:
Refer to: p9651
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
Rounding effects can occur in the last decimal place of the parameterized time.
The debounce time is rounded to whole milliseconds. It specifies the maximum duration of a fault pulse at the fail-
safe digital inputs with no reaction/influence on the selection or deselection of the Safety Basic Functions.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
1 signal
Enable
Enable
Calculated: -
Scaling: -
Unit selection: -
Max
FFFE hex
Calculated: -
Scaling: -
Unit selection: -
Max
2000000.00 [µs]
Calculated: -
Scaling: -
Unit selection: -
Max
100000.00 [µs]
Parameters
List of parameters
0 signal
Inhibit
Inhibit
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0000 hex
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2810
Factory setting
500000.00 [µs]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.00 [µs]
FP
2810
-
1-445