Parameters
List of parameters
r0965
PROFIdrive profile number / PD profile number
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the PROFIdrive profile number and profile version.
Constant value = 0329 hex.
Byte 1: Profile number = 03 hex = PROFIdrive profile
Byte 2: Profile version = 29 hex = Version 4.1
Note:
When the parameter is read via PROFIdrive, the Octet String 2 data type applies.
p0969
System runtime relative / t_System relative
Access level: 3
Can be changed: T
Units group: -
Min
0 [ms]
Description:
Displays the system runtime in ms since the last POWER ON.
Note:
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970
Reset drive parameters / Drive par reset
Access level: 1
Can be changed: C(1, 30)
Units group: -
Min
0
Description:
The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
When downloading settings 10, 11, 12, the buffer memory mode is automatically deactivated (p0014 = 0).
Value:
0:
1:
3:
5:
10:
11:
12:
100:
300:
Dependency:
Refer to: F01659
Caution:
When the buffer memory is active (see p0014), the actual parameters are backed up from RAM to ROM when a
parameter set is loaded (p0970 = 10, 11, 12).
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Peculiarities of communication via PROFIBUS DP:
- Communication with Class 1 masters (e.g. S7 controllers) is interrupted.
- Communication with Class 2 masters (e.g. STARTER) is retained.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
1-138
Inactive
Start a parameter reset
Start download of volatile parameters from RAM
Starts a safety parameter reset
Starts to download setting 10
Starts to download setting 11
Starts to download setting 12
Start a BICO interconnection reset
Only Siemens int
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
300
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: 1750, 8060
Factory setting
0 [ms]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0