Value:
7:
9:
110:
111:
999:
Dependency:
Refer to: F01505
Note:
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
r0930
PROFIdrive operating mode / PD operating mode
CU250D-2_DP_F
Access level: 3
CU250D-2_PN_F
Can be changed: -
Units group: -
Min
-
Description:
Displays the operating mode.
1: Closed-loop speed controlled operation with ramp-function generator
2: Closed-loop position controlled operation
3: Closed-loop speed controlled operation without ramp-function generator
r0944
CO: Counter for fault buffer changes / Fault buff change
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays fault buffer changes. This counter is incremented every time the fault buffer changes.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2109
r0945[0...63]
Fault code / Fault code
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the numbers of faults that have occurred.
Dependency:
Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136
Notice:
The properties of the fault buffer should be taken from the corresponding product documentation.
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0] --> actual fault case, fault 1
. . .
r0945[7], r0949[7], r0948[7], r2109[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8] --> 1st acknowledged fault case, fault 1
. . .
r0945[15], r0949[15], r0948[15], r2109[15] --> 1st acknowledged fault case, fault 8
. . .
r0945[56], r0949[56], r0948[56], r2109[56] --> 7th acknowledged fault case, fault 1
. . .
r0945[63], r0949[63], r0948[63], r2109[63] --> 7th acknowledged fault case, fault 8
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Standard telegram 7, PZD-2/2
Standard telegram 9, PZD-10/5
SIEMENS telegram 110, PZD-12/7
SIEMENS telegram 111, PZD-12/12
Free telegram configuration with BICO
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 8060
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: 1750, 8060
Factory setting
-
1-135