Parameters
List of parameters
p0233
Power unit motor reactor / PU mot reactor
Access level: 2
Can be changed: C(2), U, T
Units group: -
Min
0.000 [mH]
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the
power unit.
Refer to: p0230
Note:
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIE-
MENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
p0234
Power unit sine-wave filter capacitance / PU sine filter C
Access level: 2
Can be changed: C(2), U, T
Units group: -
Min
0.000 [µF]
Description:
Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the
power unit.
Refer to: p0230
Note:
The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIE-
MENS filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0).
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
r0238
Internal power unit resistance / PU R internal
Access level: 3
Can be changed: -
Units group: -
Min
- [ohm]
Description:
Displays the internal resistance of the power unit (IGBT and line resistance).
p0287[0...1]
Ground fault monitoring thresholds / Gnd flt threshold
Access level: 3
Can be changed: T
Units group: -
Min
0.0 [%]
Description:
Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index:
[0] = Threshold at which pre-charging starts
[1] = Threshold at which pre-charging stops
1-52
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000 [mH]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000 [µF]
Calculated: -
Scaling: -
Unit selection: -
Max
- [ohm]
Calculated: -
Scaling: -
Unit selection: -
Max
100.0 [%]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.000 [mH]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
0.000 [µF]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [ohm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
[0] 6.0 [%]
[1] 16.0 [%]