Down ramp scaling
p1139 [C]
RFG ramp-up time
0.000 ... 999999.000 [s]
p1120 [D] (10.000)
Up ramp scaling
p1138 [C]
(1)
STW setpoint chan
p1122
r1198
1 = Bypass ramp-function generator
<4>
r1198
.15
[2505.7]
1 = Enable speed setpoint
STW seq_ctrl
p1142
r0898
r0898
.6
[2501.7]
RFG setp at inp [1/min]
1
r1119
[3050.8]
0
0
STW seq_ctrl
<1>
p1141
r0898
0 = Freeze ramp-
r0898
.5
[2501.7]
function generator
1 = Internal RFG enable
[2634.8]
0 = Internal fast stop
[2634.8]
RFG accept set v
p1143 [C]
(0)
RFG setting value
<1> Inhibited during jogging.
<2>
Effective ramp-up time: Tup_eff = Tup + (IR/2 + FR/2)
Effective ramp-down time: Tdn_eff = Tdn + (IR/2 + FR/2)
<3>
p1134 = 0:
Rounding-off is always active.
Overshoots can occur.
p1134 = 1:
Final rounding-off is not effective
when the setpoint is suddenly
reduced during ramp-up.
<4> With activated Technology controller (p2200 > 0, p2251 = 0) the ramp-function generator is bypassed (r2349.5).
<5>
Value range and/or factory setting depend on Power Module.
1
2
Setpoint channel
Extended ramp-function generator
RFG ramp-down time
0.000 ... 999999.000 [s]
p1121 [D] (10.000)
<5>
(1)
0 = Internal fast stop
Ramp flattening-off
[3080.8]
Freeze ramp-function generator
0
y
1
x
p1082
1
0
0
1
<3>
-p1082
RFG round-off type
dy/dt
IR
0 ... 1
p1134 [D] (0)
p1144 [C]
(0)
Tup_eff <2>
t
t
n
t
soll
3
4
OFF3 t_RD
RFG t_start_round
RFGOFF3 t_strt_rnd
0.000 ... 5400.000 [s]
0.000 ... 30.000 [s]
0.000 ... 30.000 [s]
p1135 [D] (0.000)
p1130 [D] (0.000)
p1136 [D] (0.000)
<5>
<5>
0
1
0
1
[2634.8]
0
0
0
1
0
1
IR
Tup
Tdn
Extended ramp-function
x
generator
y
FR
IR
FR
IR
FR
Tdn_eff <2>
x
+ –
y
p1082
n_max
[3050.5]
5
fp_3070_97_51.vsd
12.12.2012
RFG t_end_delay
RFG OFF3 t_end_del
0.000 ... 30.000 [s]
0.000 ... 30.000 [s]
p1131 [D] (0.000)
p1137 [D] (0.000)
<5>
<5>
0
1
FR
y
1
0
0
STW seq_ctrl
r0898
p1140
r0898
.4
[2501.7]
1 = Enable ramp-function generator
IR
FR
RFG acceleration [1/s²]
t
Other status bits
Ramp-up active
1
Ramp-down active
0
RFG tol HL/RL act
0.000 ... 1000.000 [1/min]
p1148 [D] (19.800)
Ramp-function generator,
6
7
Function diagram
SINAMICS G120D
V4.6
n_set_5
[3080.1]
r1149
[3080.5]
status bits
8
- 3070 -