r0313[0...n]
Motor pole pair number, actual (or calculated) / Mot PolePairNo act
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the number of motor pole pairs. The value is used for internal calculations.
r0313 = 1: 2-pole motor
r0313 = 2: 4-pole motor, etc.
Dependency:
For p0314 > 0, the entered value is displayed in r0313.
For p0314 = 0, the pole pair number (r0313) is automatically calculated from the rated power (p0307), rated fre-
quency (p0310) and rated speed (p0311).
Refer to: p0307, p0310, p0311, p0314
Note:
For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency
is zero.
p0314[0...n]
Motor pole pair number / Mot pole pair No.
Access level: 3
Can be changed: C(1, 3)
Units group: -
Min
0
Description:
Sets the motor pole pair number.
p0314 = 1: 2-pole motor
p0314 = 2: 4-pole motor, etc.
Dependency:
For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice:
If p0314 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly.
For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
p0316[0...n]
Motor torque constant / Mot kT
Access level: 3
Can be changed: C(1, 3), U, T
Units group: 28_1
Min
0.00 [Nm/A]
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0: The torque constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque constant.
Dependency:
Refer to: r0334
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
This parameter is not used for induction motors (p0300 = 1xx).
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
255
Calculated: -
Scaling: -
Unit selection: p0100
Max
400.00 [Nm/A]
Parameters
List of parameters
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: 5300
Factory setting
-
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00 [Nm/A]