Download Print this page

Siemens SINAMICS G120D List Manual page 142

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Parameters
List of parameters
r0991[0...99]
List of modified parameters 2 / List chang. par 2
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays those parameters with a value other than the factory setting for this drive.
Dependency:
Refer to: r0990, r0999
Note:
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here. In a
long list, index 99 contains the parameter number at which position the list continues.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
r0999[0...99]
List of modified parameters 10 / List chang. par 10
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays those parameters with a value other than the factory setting for this drive.
Dependency:
Refer to: r0990, r0991
Note:
Modified parameters are displayed in indices 0 to 98. If an index contains the value 0, then the list ends here.
This list consists solely of the following parameters:
r0990[0...99], r0991[0...99] ... r0999[0...99]
The parameters in this list are not displayed in the expert list of the commissioning software. However, they can be
read from a higher-level control system (e.g. PROFIBUS master).
p1000[0...n]
Speed setpoint selection / n_set sel
CU240D-2_DP
Access level: 1
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Sets the source for the speed setpoint.
For single-digit values, the following applies:
The value specifies the main setpoint.
For double-digit values, the following applies:
The left-hand digit specifies the supplementary setpoint, the right-hand digit the main setpoint.
Example:
Value = 26
--> The analog setpoint (2) supplies the supplementary setpoint.
--> The fieldbus (6) supplies the main setpoint.
Value:
0:
1:
2:
3:
6:
7:
10:
11:
1-142
No main setpoint
Motorized potentiometer
Analog setpoint
Fixed speed setpoint
Fieldbus
Analog setpoint 2
Motor potentiometer + no main setpoint
Motor potentiometer + motor potentiometer
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
77
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: CDS, p0170
Func. diagram: -
Factory setting
6

Advertisement