Download Print this page

Siemens SINAMICS G120D List Manual page 382

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Parameters
List of parameters
725:
740:
745:
750:
800:
Index:
[0] = System
[1] = Partial boot
r3996[0...1]
Parameter write inhibit status / Par_write inhib st
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays whether writing to parameters is inhibited.
r3996[0] = 0:
Parameter write not inhibited.
0 < r3996[0] < 100:
Parameter write inhibited. The value shows how the calculations are progressing.
Index:
[0] = Progress calculations
[1] = Cause
Note:
Re index 1:
Only for internal Siemens troubleshooting.
r4640[0...95]
Encoder diagnostics state machine / Enc diag stat_ma
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the encoder diagnostics for the PROFIdrive interface.
p4652[0...2]
XIST1_ERW reset mode / XIST1_ERW res mode
Access level: 3
Can be changed: C(3)
Units group: -
Min
0
Description:
Sets the mode to reset the actual value in XIST_ERW (CO: r4653).
Value:
0:
1:
2:
3:
Index:
[0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency:
Refer to: r4653, r4654, p4655
Note:
If value = 1:
The value in XIST1_ERW is reset when passing every zero mark.
If value = 2:
The value in XIST1_ERW is reset with a 0/1 edge via binector input p4655.
If value = 3:
The value in XIST1_ERW is reset after a 0/1 edge via binector input p4655 when passing the next zero mark.
1-382
Wait for cyclic
Check the ability to operate
Start cyclic calculations
Interrupt enable
Initialization finished
Inactive
Reset with zero mark
Reset with BICO
Reset with selected zero mark
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
3
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: 4750
Factory setting
0