Signal sources for ZSW3 im Interface Mode SINAMICS
Signal
1 = DC brake active
ZSW3.0
0 = DC brake not active
ZSW3.1
1 = |n_act| > p1226 (n_standstill)
ZSW3.2
1 = |n_act| > p1080 (n_min)
ZSW3.3
1 = I_act >= p2170
ZSW3.4
1 = |n_act| > p2155
ZSW3.5
1 = |n_act| <= p2155
ZSW3.6
1 = |n_act| >= r1119 (n_set)
ZSW3.7
1 = Vdc <= p2172
ZSW3.8
1 = Vdc > p2172
ZSW3.9
1 = Ramping finished
ZSW3.10
1 = Techn. contr. out at lower limit
ZSW3.11
1 = Techn. contr. out at upper limit
ZSW3.12
Reserved
ZSW3.13
Reserved
ZSW3.14
Reserved
ZSW3.15
Reserved
<1>
Used in telegrams 350.