Parameters
List of parameters
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2183, p2184, p2185, p2186
Note:
In order that the load monitoring can reliably respond, the speed threshold p2182 should always be set lower than
the minimum motor speed to be monitored.
p2183[0...n]
Load monitoring speed threshold value 2 / n_thresh 2
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2184, p2187, p2188
p2184[0...n]
Load monitoring speed threshold value 3 / n_thresh 3
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed/torque envelope curve for load monitoring.
The envelope curve (upper and lower envelope curve) is defined as follows based on 3 speed thresholds:
p2182 (n_threshold 1) --> p2185 (M_threshold 1, upper), p2186 (M_threshold 1, lower)
p2183 (n_threshold 2) --> p2187 (M_threshold 2, upper), p2188 (M_threshold 2, lower)
p2184 (n_threshold 3) --> p2189 (M_threshold 3, upper), p2190 (M_threshold 3, lower)
Dependency:
The following applies: p2182 < p2183 < p2184
Refer to: p2182, p2183, p2189, p2190
Note:
In order that the load monitoring can reliably respond, the speed threshold p2184 should always be set higher than
the maximum motor speed to be monitored.
p2185[0...n]
Load monitoring torque threshold 1 upper / M_thresh 1 upper
Access level: 3
Can be changed: U, T
Units group: 7_1
Min
0.00 [Nm]
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2185 > p2186
Refer to: p2182, p2186
Note:
The upper envelope curve is defined by p2185, p2187 and p2189.
1-292
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
900.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
1500.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
10000000.00 [Nm]