p2106[0...n]
BI: External fault 1 / External fault 1
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for external fault 1.
Dependency:
Refer to: F07860
Note:
An external fault is triggered with a 1/0 signal.
p2107[0...n]
BI: External fault 2 / External fault 2
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for external fault 2.
Dependency:
Refer to: F07861
Note:
An external fault is triggered with a 1/0 signal.
p2108[0...n]
BI: External fault 3 / External fault 3
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the signal source for external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency:
Refer to: p3110, p3111, p3112
Refer to: F07862
Note:
An external fault is triggered with a 1/0 signal.
r2109[0...63]
Fault time removed in milliseconds / t_flt resolved ms
Access level: 3
Can be changed: -
Units group: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the fault was removed.
Dependency:
Refer to: r0945, r0947, r0948, r0949, r2130, r2133, r2136
Notice:
The time comprises r2136 (days) and r2109 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Parameters
List of parameters
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2546
Factory setting
1
Data type: Unsigned32
Dyn. index: -
Func. diagram: 1750, 8060
Factory setting
- [ms]