COMM-IF: Commissioning interface
The parameter is not influenced by setting the factory setting.
p2011
Comm IF address / Comm add
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the address for the commissioning interface (USS, RS232).
Note:
The parameter is not influenced by setting the factory setting.
p2016[0...3]
CI: Comm IF USS PZD send word / Comm USS send word
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Selects the PZD (actual values) to be sent via the commissioning interface USS.
The actual values are displayed on an intelligent operator panel (IOP).
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
r2019[0...7]
Comm IF error statistics / Comm err
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the receive errors at the commissioning interface (USS, RS232).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
p2030
Field bus int protocol selection / Field bus protocol
CU240D-2_DP
Access level: 1
CU240D-2_DP_F
Can be changed: T
CU250D-2_DP_F
Units group: -
Min
0
Description:
Sets the communication protocol for the field bus interface.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
19200 baud
38400 baud
57600 baud
76800 baud
93750 baud
115200 baud
Calculated: -
Scaling: -
Unit selection: -
Max
31
Calculated: -
Scaling: 4000H
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
3
Parameters
List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
2
Data type: U32 / Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
3