Parameters
List of parameters
Bit field:
Bit
Signal name
00
F-DI 0
01
F-DI 1
02
F-DI 2
Dependency:
p10006 / p10106
p10022 / p10122
p10023 / p10123
p10026 / p10126
p10030 / p10130
p10031 / p10131
Refer to: r10149
p10050
SI PROFIsafe F-DI transfer (processor 1) / SI Ps F-DI tran P1
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
-
Description:
Setting for the transfer and evaluation of failsafe digital inputs (F-DI) via PROFIsafe.
The safe state of the selected F-DIs is transferred to the F-control via PROFIsafe. The F-DIs are monitored for dis-
crepancies. Discrepancy faults can be acknowledged via PROFIsafe.
Bit field:
Bit
Signal name
00
F-DI 0 processor 1
01
F-DI 1 processor 1
02
F-DI 2 processor 1
Dependency:
Refer to: p10150
Note:
F-DI: Failsafe Digital Input
r10051.0...2
CO/BO: SI digital inputs status (processor 1) / SI DI status P1
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: -
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
-
Description:
Displays the single-channel, logical, and debounced status of the fail-safe digital inputs (F-DI).
The parameter is updated in the SI Motion monitoring clock cycle.
Bit field:
Bit
Signal name
00
F-DI 0 processor 1
01
F-DI 1 processor 1
02
F-DI 2 processor 1
Dependency:
Refer to: p9501, p9601, p10017, p10050, r10151
Note:
If a safety function is assigned to an input (e.g. via p10022), then the following applies:
- logical "0": Safety function is selected
- logical "1": Safety function is de-selected
The interrelationship between the logical level and the external voltage level at the input depends on the parameter-
ization (refer to p10040) of the input as either NC or NO contact and is aligned to the use of a safety function:
With 24 V at the input, NC contacts have a logical "1" level, for 0 V at the input, a logical "0" level.
This means that an NC/NC contact parameterization of 0 V at both inputs of the F-DI selects the safety function, for
24 V at both inputs, de-selects the safety function.
With 24 V at the input, NO contacts have a logical "0" level, for 0 V at the input, a logical "1" level.
This means that for an NC/NO contact parameterization, the level 0 V/24 V selects the safety function, the level 24
V/0 V de-selects the safety function.
1-456
1 signal
Safety monitored
Safety monitored
Safety monitored
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Transfer
Transfer
Transfer
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
High
High
High
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
0 signal
Freely available
Freely available
Freely available
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0000 bin
0 signal
No transfer
No transfer
No transfer
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
Low
Low
Low
FP
-
-
-
FP
-
-
-
FP
-
-
-