F01030
Sign-of-life failure for master control
Reaction:
OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
For active PC master control, no sign-of-life was received within the monitoring time.
The master control was returned to the active BICO interconnection.
Remedy:
Set the monitoring time higher at the PC or, if required, completely disable the monitoring function.
For the commissioning software, the monitoring time is set as follows:
<Drive> -> Commissioning -> Control panel -> Button "Fetch master control" -> A window is displayed to set the mon-
itoring time in milliseconds.
Notice:
The monitoring time should be set as short as possible. A long monitoring time means a late response when the
communication fails!
F01033
Units changeover: Reference parameter value invalid
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing over the units to the referred representation type, it is not permissible for any of the required refer-
ence parameters to be equal to 0.0
Fault value (r0949, parameter):
Reference parameter whose value is 0.0.
See also: p0505 (Selecting the system of units), p0595 (Technological unit selection)
Remedy:
Set the value of the reference parameter to a number different than 0.0.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
F01034
Units changeover: Calculation parameter values after reference value change
unsuccessful
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The change of a reference parameter meant that for an involved parameter the selected value was not able to be re-
calculated in the per unit representation. The change was rejected and the original parameter value restored.
Fault value (r0949, parameter):
Parameter whose value was not able to be re-calculated.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
Remedy:
Select the value of the reference parameter such that the parameter involved can be calculated in the per unit rep-
resentation.
See also: p0304, p0305, p0310, p0596, p2000, p2001, p2002, p2003, r2004
A01035 (F)
ACX: Parameter back-up file corrupted
Reaction:
NONE
Acknowledge:
NONE
Cause:
When the Control Unit is booted, no complete data set was found from the parameter back-up files. The last time
that the parameterization was saved, it was not completely carried out.
It is possible that the backup was interrupted by switching off or withdrawing the memory card.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = 01 hex:
Power up was realized without data backup. The drive is in the factory setting.
aa = 02 hex:
The last available internal backup data record was loaded. The parameterization must be checked. It is recom-
mended that the parameterization is downloaded again.
aa = 03 hex:
The last available data record from the memory card was loaded. The parameterization must be checked.
aa = 04 hex:
An invalid data backup was loaded from the memory card into the drive. The drive is in the factory setting.
dd, cc, bb:
Only for internal Siemens troubleshooting.
See also: p0971 (Save parameters)
Remedy:
- Download the project again with the commissioning software.
- save all parameters (p0971 = 1 or "copy RAM to ROM").
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Faults and alarms
List of faults and alarms
3-781