Parameters
List of parameters
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
For U/f control, the mechanical speed calculated from the output frequency and the slip is shown in r0063[2] even if
slip compensation is deactivated.
r0022
Speed actual value rpm smoothed / n_act rpm smooth
Access level: 3
Can be changed: -
Units group: -
Min
- [rpm]
Description:
Displays the smoothed actual value of the motor speed.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
For U/f control and when slip compensation is deactivated (see p1335), the synchronous speed to the output fre-
quency is shown in r0022.
Dependency:
Refer to: r0021, r0063
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
For U/f control, the mechanical speed calculated from the output frequency and the slip is shown in r0063[2] even if
slip compensation is deactivated.
r0024
Output frequency smoothed / f_outp smooth
Access level: 3
Can be changed: -
Units group: -
Min
- [Hz]
Description:
Displays the smoothed converter frequency.
Dependency:
Refer to: r0066
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
r0025
CO: Output voltage smoothed / U_outp smooth
Access level: 2
Can be changed: -
Units group: -
Min
- [Vrms]
Description:
Displays the smoothed output voltage of the power unit.
Dependency:
Refer to: r0072
Note:
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
1-26
Calculated: -
Scaling: p2000
Unit selection: -
Max
- [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max
- [Hz]
Calculated: -
Scaling: p2001
Unit selection: -
Max
- [Vrms]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 1690, 5300, 5730,
6799
Factory setting
- [Hz]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 1690, 5730, 6799
Factory setting
- [Vrms]