Download Print this page

Siemens SINAMICS G120D List Manual page 535

Hide thumbs Also See for SINAMICS G120D:

Advertisement

p20363
MFP 3 run sequence / MFP 3 RunSeq
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Setting parameter for the run sequence of instance MFP 3 within the run-time group set in p20362.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20372
CI: PLI 0 input X / PLI 0 input X
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source for input X of the polyline (20 breakpoints) of instance PLI 0.
r20373
CO: PLI 0 output Y / PLI 0 output Y
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Display parameter for the output quantity Y of the polyline (20 breakpoints) of instance PLI 0
p20374[0...19]
PLI 0 X-coordinate, A breakpoint / PLI 0 X-coordinate
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-340.28235E36
Description:
Sets the x-coordinates for the breakpoints (A0...A19) of the polyline (20 breakpoints) of instance PLI 0.
Index:
[0] = Breakpoint 0
[1] = Breakpoint 1
[2] = Breakpoint 2
[3] = Breakpoint 3
[4] = Breakpoint 4
[5] = Breakpoint 5
[6] = Breakpoint 6
[7] = Breakpoint 7
[8] = Breakpoint 8
[9] = Breakpoint 9
[10] = Breakpoint 10
[11] = Breakpoint 11
[12] = Breakpoint 12
[13] = Breakpoint 13
[14] = Breakpoint 14
[15] = Breakpoint 15
[16] = Breakpoint 16
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
340.28235E36
Parameters
List of parameters
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7230
Factory setting
960
Data type: U32 / FloatingPoint32
Dyn. index: -
Func. diagram: 7226
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7226
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7226
Factory setting
0.0000
1-535