Download Print this page

Siemens SINAMICS G120D List Manual page 406

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Parameters
List of parameters
p9356
SI Motion pulse suppression delay time (processor 2) / SI Mtn IL t_del P2
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
0.00 [µs]
Description:
Sets the delay time for the safe pulse suppression after STOP B / SS1.
In the case of encoderless motion monitoring functions with safe brake ramp monitoring (p9306 = 1) and the OFF3
ramp enabled at the same time (p9507.3 = 0), the parameter has no effect.
Dependency:
Refer to: p9360, p9556
Refer to: C01701
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
SS1: Safe Stop 1
p9358
SI Motion acceptance test mode time limit (processor 2) / SI Mtn acc t P2
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
5000000.00 [µs]
Description:
Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency:
Refer to: p9558
Refer to: C01799
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
p9360
SI Motion pulse suppression shutdown speed (processor 2) / SI Mtn IL n_sh P2
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
10.00 [rpm]
Description:
Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP
A).
Dependency:
Refer to: p9356, p9560
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
The shutdown speed has no effect for a value = 0.
SS1: Safe Stop 1
1-406
Calculated: -
Scaling: -
Unit selection: -
Max
3600000000.00 [µs]
Calculated: -
Scaling: -
Unit selection: -
Max
100000000.00 [µs]
Calculated: -
Scaling: -
Unit selection: -
Max
6000.00 [rpm]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2819
Factory setting
600000000.00 [µs]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
40000000.00 [µs]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
10.00 [rpm]