p1213[0...1]
Automatic restart monitoring time / AR t_monit
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [s]
Description:
Sets the monitoring time of the automatic restart (AR).
Index:
[0] = Restart
[1] = Reset start counter
Dependency:
Refer to: p1210, r1214
Caution:
A change is only accepted and made in the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Notice:
After fault F07320 occurs, the power-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note:
Re index 0:
The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. If, after the monitoring time has expired, the drive has still not successfully started again
(flying restart and magnetizing of the motor must have been completed: r0056.4 = 1), then fault F07320 is output.
The monitoring is de-activated with p1213 = 0. If p1213 is set lower than the sum of p1212, the magnetizing time
p0346 and the additional delay time due to the flying restart, then fault F07320 is generated at each restart. If, for
p1210 = 1, the time in p1213 is set lower than in p1212, then fault F07320 is also generated at each restart.
The monitoring time must be extended if the faults that occur cannot be immediately and successfully acknowl-
edged (e.g. for faults that are permanently present).
In the case of p1210 = 14, 16, the faults which are present must be acknowledged manually within the time in
p1213[0]. Otherwise, fault F07320 is generated after the set time.
Re index 1:
The start counter (refer to r1214) is only set back to the starting value p1211 if, after successful restart, the time in
p1213[1] has expired. The delay time is not effective for fault acknowledgement without automatic restart (p1210 =
1). After a power failure (blackout) the delay time only starts after the line supply returns and the Control Unit boots.
The start counter is set to p1211, if F07320 occurred, the power-on command is withdrawn and the fault is acknowl-
edged.
The start counter is immediately updated if the starting value p1211 or the mode p1210 is changed.
For p1210 = 26, the fault must have been successfully acknowledged and the switch-on command issued within the
time in p1213[0]. Otherwise, fault F07320 is generated after the set time.
r1214.0...15
CO/BO: Automatic restart status / AR status
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the status of the automatic restart (AR).
Bit field:
Bit
Signal name
00
Initialization
01
Wait for alarm
02
Auto restart act
03
Setting the acknowledgement command
04
Acknowledge alarms
05
Restart
06
Delay time running after automatic power-
up
07
Fault
10
Effective fault
12
Start count. bit 0
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
10000.0 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ON
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
[0] 60.0 [s]
[1] 0.0 [s]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
No
OFF
FP
-
-
-
-
-
-
-
-
-
-
1-179