List of parameters
p20282
LVM 1 run-time group / LVM 1 RTG
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
5
Description:
Setting parameter for the run-time group in which instance LVM 1 of the double-sided limiter is to be called.
Value:
5:
6:
9999: Do not calculate
p20283
LVM 1 run sequence / LVM 1 RunSeq
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Setting parameter for the run sequence of instance LVM 1 within the run-time group set in p20282.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20284
CI: DIF 0 input X / DIF 0 input X
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source of input quantity X of instance DIF 0 of the differentiating element.
p20285
DIF 0 differentiating time constant in ms / DIF 0 T_diff ms
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.00
Description:
Sets the differentiating time constant Td in milliseconds of instance DIF 0 of the differentiating element.
r20286
CO: DIF 0 output Y / DIF 0 output Y
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Display parameter for output quantity Y of instance DIF 0 of the differentiating element.
1-520
Run-time group 5
Run-time group 6
Calculated: -
Scaling: -
Unit selection: -
Max
9999
Calculated: -
Scaling: -
Unit selection: -
Max
7999
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
340.28235E36
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Integer16
Dyn. index: -
Func. diagram: 7270
Factory setting
9999
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7270
Factory setting
730
Data type: U32 / FloatingPoint32
Dyn. index: -
Func. diagram: 7264
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7264
Factory setting
0.00
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7264
Factory setting
-