Remedy:
- carry out a POWER ON (power off/on).
- check the power supply voltage wiring for the DRIVE-CLiQ component (interrupted cable, contacts, ...).
- check the dimensioning of the power supply for the DRIVE-CLiQ component.
F30903
Power unit: I2C bus error occurred
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY
Cause:
Communications error with an EEPROM or A/D converter.
Fault value (r0949, interpret hexadecimal):
80000000 hex:
- internal software error.
00000001 hex ... 0000FFFF hex:
- module fault.
Remedy:
Re fault value = 80000000 hex:
- upgrade firmware to later version.
Re fault value = 00000001 hex ... 0000FFFF hex:
- replace the module.
A30920 (F)
Temperature sensor fault
Reaction:
NONE
Acknowledge:
NONE
Cause:
When evaluating the temperature sensor, an error occurred.
Alarm value (r2124, interpret decimal):
1: Wire breakage or sensor not connected (KTY: R > 2120 Ohm).
2: Measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).
Remedy:
- make sure that the sensor is connected correctly.
- replace the sensor.
F30950
Power unit: Internal software error
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret decimal):
Information about the fault source.
Only for internal Siemens troubleshooting.
Remedy:
- If necessary, upgrade the firmware in the power unit to a later version.
- contact the Hotline.
A30999 (F, N)
Power unit: Unknown alarm
Reaction:
NONE
Acknowledge:
NONE
Cause:
An alarm occurred on the power unit that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Alarm value (r2124, interpret decimal):
Alarm number.
Note:
If required, the significance of this new alarm can be read about in a more recent description of the Control Unit.
Remedy:
- replace the firmware on the power unit by an older firmware version (r0128).
- upgrade the firmware on the Control Unit (r0018).
F31100 (N, A)
Encoder 1: Zero mark distance error
Reaction:
ENCODER (IASC/DCBRK, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowledge:
PULSE INHIBIT
Cause:
The measured zero mark distance does not correspond to the parameterized zero mark distance.
For distance-coded encoders, the zero mark distance is determined from zero marks detected pairs. This means that
if a zero mark is missing, depending on the pair generation, this cannot result in a fault and also has no effect in the
system.
The zero mark distance for the zero mark monitoring is set in p0425 (rotary encoder) or p0424 (linear encoder).