Parameters
List of parameters
r0208
Rated power unit line supply voltage / PU U_rated
Access level: 2
Can be changed: -
Units group: -
Min
- [Vrms]
Description:
Displays the rated line supply voltage of the power unit.
r0208 = 400 : 380 - 480 V +/-10 %
r0208 = 500 : 500 - 600 V +/-10 %
r0208 = 690 : 660 - 690 V +/-10 %
r0209[0...4]
Power unit maximum current / PU I_max
Access level: 3
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the maximum output current of the power unit.
Index:
[0] = Catalog
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
Refer to: p0205
p0210
Drive unit line supply voltage / V_connect
Access level: 3
Can be changed: C(2), T
Units group: -
Min
1 [V]
Description:
Sets the drive unit supply voltage (rms value of the phase-to-phase line supply voltage).
Dependency:
Set p1254, p1294 (automatic detection of the Vdc switch-on levels) = 0.
The switch-in thresholds of the Vdc_max controller are then directly determined using p0210.
Warning:
In the case of regenerative power units (PM250, PM260), the regenerative power limit for U/f control current limita-
tion control is calculated as a proportion of the supply voltage p0210. Therefore, p0210 should not be set to a value
higher than the actual line voltage.
Caution:
If the line supply voltage is higher than the entered value, the Vdc controller may be automatically de-activated in
some cases to prevent the motor from accelerating. In this case, an appropriate alarm is output.
Note:
Setting ranges for p0210 as a function of the rated power unit voltage:
U_rated = 230 V:
- p0210 = 200 ... 240 V
U_rated = 400 V:
- p0210 = 380 ... 480 V
U_rated = 500 V:
- p0210 = 500 ... 600 V
U_rated = 690 V:
- p0210 = 660 ... 690 V
The pre-charging switch-in threshold for the DC link voltage (Vdc) is calculated from p0210:
Vdc_pre = p0210 * 0.82 * 1.35
1-50
Calculated: -
Scaling: -
Unit selection: -
Max
- [Vrms]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
63000 [V]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 8750, 8850, 8950
Factory setting
- [Arms]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
400 [V]