Note:
For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency
is zero.
p0314[0...n]
Motor pole pair number / Mot pole pair No.
SERVO_S110-CAN,
Can be changed: C2(1, 3)
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the motor pole pair number.
p0314 = 1: 2-pole motor
r0314 = 2: 4-pole motor, etc.
Dependency:
For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice:
If p0314 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010
= 3).
For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
p0316[0...n]
Motor torque constant / Mot kT
SERVO_S110-CAN,
Can be changed: C2(1, 3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: ASM, REL, FEM
Min
0.00 [Nm/A]
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0: The torque constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque constant.
Dependency:
Refer to: r0334, r1937
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
This parameter is not used for induction motors (p0300 = 1xx).
p0318[0...n]
Motor stall current / Mot I_standstill
SERVO_S110-CAN,
Can be changed: C2(3)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: ASM, REL, FEM
Min
0.00 [Arms]
Description:
Sets the stall current for synchronous motors (p0300 = 2xx).
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The parameter is used for the I2t monitoring of the motor (refer to p0611).
This parameter is not used for induction motors (p0300 = 1xx).
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: MDS, p0130
Units group: -
Scaling: -
Max
4000
Calculated: -
Dynamic index: MDS, p0130
Units group: 28_1
Scaling: -
Max
400.00 [Nm/A]
Calculated: -
Dynamic index: MDS, p0130
Units group: -
Scaling: -
Max
10000.00 [Arms]
Parameter
List of parameters
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
0.00 [Nm/A]
Access level: 3
Func. diagram: 8017
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
1-79