Note:
The closed-loop torque control can only be changed over in operation (p1300 = 20, 21) by selecting the closed-loop
speed control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state is dis-
played in r1407, bit 2 and bit 3.
For encoderless operation (p1404 = 0 or p1300 = 20), the following applies:
- The following condition must be fulfilled: p1800 >= n / (2 * p0115[0]), n = 1, 2, ...
- For motors with a small power rating (< 300 W) we recommend to set n >= 2.
p1317[0...n]
U/f control activation / Uf act
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Integer16
SERVO_S110-PN
P-Group: -
Not for motor type: -
Min
0
Description:
Setting to activate the U/f control with linear characteristic.
Value:
0:
1:
Dependency:
Refer to: p1318, p1319, p1326, p1327
Note:
The following applies for firmware version 4.3 and higher:
When U/f control is activated, resonance damping is automatically activated. The resonance damping must be de-
activated (p1338 = 0) in order to obtain pure diagnostics operation without the influence of actual values.
Further, when U/f control is activated, the following functions are active:
- Vdc controller (p1240, p1244, p1248, p1250).
- the up ramp is limited by the set M, P and I limits (p0326, p0341, p0342, p0640, p1520, p1521, p1530, p1531,
p1498).
- the ramp-function generator is held if the current actual value exceeds the current limit set in p0640.
p1318[0...n]
U/f control ramp-up/ramp-down time / Uf t_rmp-up_rmp-dn
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: V/f open-loop control
Not for motor type: -
Min
0.000 [s]
Description:
Sets the ramp-up and ramp-down time for the U/f control.
The ramp-function generator requires this time to reach the maximum speed (p1082) from zero.
Dependency:
Refer to: p1317, p1319, p1326, p1327
Note:
This ramp is used for stall protection and operates independently of any ramp-function generator that might have
been configured.
p1319[0...n]
U/f control voltage at zero frequency / Uf U at f=0 Hz
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: V/f open-loop control
Not for motor type: -
Min
0.0 [Vrms]
Description:
The linear characteristic for the U/f control is defined by 0 Hz / p1319 and p1326 / p1327.
This parameter specifies the voltage for a frequency of 0 Hz.
Dependency:
The U/f control is activated via p1317 = 1.
Refer to: p1317, p1326, p1327
Note:
Linear interpolation is carried out between the points 0 Hz/p1319 and p1326/p1327.
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
De-activated (p1300 effective)
Activated
Calculated: -
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
1
Calculated: -
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
999999.000 [s]
Calculated: CALC_MOD_REG
Dynamic index: DDS, p0180
Units group: -
Scaling: -
Max
50.0 [Vrms]
Parameter
List of parameters
Access level: 3
Func. diagram: 1590, 5730
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 5300
Unit selection: -
Expert list: 1
Factory setting
10.000 [s]
Access level: 3
Func. diagram: 5300
Unit selection: -
Expert list: 1
Factory setting
0.0 [Vrms]
1-233