p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
-200.00 [%]
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value exceeds this upper limit, this results in fault F07426.
Note:
Limiting only active for p2252 bit 3 = 1.
p2268
Technology controller lower limit actual value / Tec_ctrl l_lim act
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
-200.00 [%]
Description:
Sets the lower limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value falls below this lower limit, this results in fault F07426.
Note:
Limiting only active for p2252 bit 3 = 1.
p2269
Technology controller gain actual value / Tech_ctrl gain act
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
0.00 [%]
Description:
Scaling factor for the actual value of the technology controller.
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2271
Note:
For 100%, the actual value is not changed.
p2270
Technology controller actual value function / Tec_ctr ActVal fct
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: Integer16
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
0
Description:
Setting to use an arithmetic function for the actual value signal of the technology controller.
Value:
0:
1:
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
No function
Root function (root from x)
Calculated: -
Dynamic index: -
Units group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dynamic index: -
Units group: 9_1
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
500.00 [%]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
3
Parameter
List of parameters
Access level: 3
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
200.00 [%]
Access level: 3
Func. diagram: 7958
Unit selection: p0595
Expert list: 1
Factory setting
-200.00 [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
1-349