Siemens SINAMICS S110 List Manual page 137

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

p0624[0...n]
Motor Temperature Offset PT100 / Mot T_offset PT100
SERVO_S110-CAN,
Can be changed: C2(3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
-100.0 [K]
Description:
Sets the temperature offset for the PT100 measured value.
If there is a difference between the motor temperature displayed in r0035 and the actual motor temperature, this off-
set can be entered in this parameter, thereby compensating for the difference.
Dependency:
Refer to: p0600, p0601
Note:
The parameter only takes effect with the following settings:
- Temperature sensor of the power unit detected (p0600 = 11).
- Sensor type PT100 selected (p0601 = 5).
If the resistance in series with the PT100 (e.g. the cable resistance of the feeder cable) is known, the following con-
version formula must be used:
Offset in p0624 = Measured resistance in ohms x 2.5 K/Ohm
Example:
Measured cable resistance = 2 Ohm
--> 2 Ohm x 2.5 K / Ohm = 5.0 K
p0625[0...n]
Motor ambient temperature / Mot T_ambient
SERVO_S110-CAN,
Can be changed: C2(3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
-40 [°C]
Description:
Defines the ambient temperature of the motor for calculating the motor temperature model.
Note:
The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
If the thermal I2t motor model is activated for permanent-magnet synchronous motors (refer to p0611), p0625 is
included in the model calculation if a temperature sensor is not being used (see p0601).
p0626[0...n]
Motor overtemperature, stator core / Mot T_over core
SERVO_S110-CAN,
Can be changed: C2(3), U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor
Not for motor type: PEM, REL, FEM
Min
20 [K]
Description:
Defines the rated overtemperature of the stator core referred to the ambient temperature.
Dependency:
For 1LA5 and 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: MDS, p0130
Units group: 21_2
Scaling: -
Max
100.0 [K]
Calculated: CALC_MOD_EQU
Dynamic index: MDS, p0130
Units group: 21_1
Scaling: -
Max
80 [°C]
Calculated: -
Dynamic index: MDS, p0130
Units group: 21_2
Scaling: -
Max
200 [K]
Parameter
List of parameters
Access level: 3
Func. diagram: 8016
Unit selection: p0505
Expert list: 1
Factory setting
0.0 [K]
Access level: 3
Func. diagram: 8016
Unit selection: p0505
Expert list: 1
Factory setting
20 [°C]
Access level: 3
Func. diagram: 8016
Unit selection: p0505
Expert list: 1
Factory setting
50 [K]
1-137

Hide quick links:

Advertisement

Table of Contents