p2930[0...n]
CO: Fixed value M [Nm] / Fixed value M [Nm]
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Free function blocks
Not for motor type: REL
Min
-100000.00 [Nm]
Description:
Sets a fixed value for torque.
Dependency:
Refer to: p2900, p2901
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
The value can, for example, be used to interconnect a supplementary torque.
p3016
MotId torque constant identified / kT ident
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor identification
Not for motor type: ASM, REL, FEM
Min
0.00 [Nm/A]
Description:
Torque constant for the synchronous motor determined by the motor data identification.
This torque constant can be changed after the identification and accepted in p0316 with p1910/p1960 = -3.
Dependency:
Refer to: p0316, r0334, r1937, p1960
p3017
MotId voltage constant identified / kE ident
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor identification
Not for motor type: ASM, REL, FEM
Min
0.0 [Vrms]
Description:
Voltage constant for a synchronous motor determined by the motor data identification.
This voltage constant can be changed after the identification and accepted in p0317 with p1910/p1960 = -3.
Units for rotating synchronous motors: Vrms/(1000 rpm), phase-to-phase
Dependency:
Refer to: r1938, p1960
p3020
MotId magnetizing current identified / I_mag ident
SERVO_S110-CAN,
Can be changed: U, T
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Motor identification
Not for motor type: REL, FEM
Min
0.000 [Arms]
Description:
Magnetizing current for an induction motor determined by the motor data identification.
This magnetizing current can be changed after the identification and accepted in p0320 with p1910/p1960 = -3.
Dependency:
Refer to: p0320, r0331, p1910, r1948, p1960
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Calculated: -
Dynamic index: DDS, p0180
Units group: 7_1
Scaling: p2003
Max
100000.00 [Nm]
Calculated: CALC_MOD_ALL
Dynamic index: -
Units group: 28_1
Scaling: -
Max
100.00 [Nm/A]
Calculated: CALC_MOD_ALL
Dynamic index: -
Units group: -
Scaling: -
Max
10000.0 [Vrms]
Calculated: CALC_MOD_ALL
Dynamic index: -
Units group: -
Scaling: -
Max
5000.000 [Arms]
Parameter
List of parameters
Access level: 3
Func. diagram: 1021
Unit selection: p0505
Expert list: 1
Factory setting
0.00 [Nm]
Access level: 3
Func. diagram: -
Unit selection: p0100
Expert list: 1
Factory setting
0.00 [Nm/A]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.0 [Vrms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.000 [Arms]