Parameter
List of parameters
Note:
Drive data sets are selected via binector input p0820 and following.
The currently effective drive data set is displayed in r0051.
If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
r0838[0...3]
Motor/Encoder Data Set selected / MDS/EDS selected
SERVO_S110-CAN,
Can be changed: -
SERVO_S110-DP,
Data type: Unsigned8
SERVO_S110-PN
P-Group: Displays, signals
Not for motor type: -
Min
-
Description:
Displays the selected Motor Data Set (MDS) and the selected Encoder Data Sets (EDS).
Index:
[0] = Motor Data Set MDS selected
[1] = Encoder 1 Encoder Data Set EDS selected
[2] = Encoder 2 Encoder Data Set EDS selected
[3] = Reserved
Dependency:
Refer to: r0049, p0186, p0187, p0188
Note:
Value 99 means the following: No encoder assigned (not configured).
p0839
Motor changeover contactor control delay time / Mot_chg ctrl t_del
SERVO_S110-CAN,
Can be changed: C2(3)
SERVO_S110-DP,
Data type: Unsigned16
SERVO_S110-PN
P-Group: Motor
Not for motor type: -
Min
0 [ms]
Description:
Sets the delay time for the contactor control for the motor changeover.
Note:
The delay time is taken into account in the following cases:
- for feedback signal, previous contactor "Open". The new motor contactor is controlled (energized) after the delay
time has expired.
- for the feedback signal, new motor contactor "Closed". The pulses are enabled after the delay time has expired.
p0840[0...n]
BI: ON / OFF (OFF1) / ON / OFF (OFF1)
SERVO_S110-CAN,
Can be changed: T
SERVO_S110-DP,
Data type: Unsigned32 / Binary
SERVO_S110-PN
P-Group: Commands
Not for motor type: -
Min
-
Description:
Sets the signal source for the command "ON/OFF (OFF1)".
For the PROFIdrive profile, this command corresponds to control word 1 bit 0 (STW1.0).
Recommend.:
When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency:
Refer to: p1055, p1056
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
For binector input p0840 = 0 signal, the motor can be moved, jogging using binector input p1055 or p1056.
The command "ON/OFF (OFF1)" can be issued using binector input p0840 or p1055/p1056.
For binector input p0840 = 0 signal, the switch-on inhibit is acknowledged.
Only the signal source that originally powered up can also power down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
1-166
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
-
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
500 [ms]
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: -
Max
-
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 2
Func. diagram: 8565
Unit selection: -
Expert list: 1
Factory setting
-
Access level: 2
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0 [ms]
Access level: 3
Func. diagram: 2501, 2610,
8720, 8820, 8920
Unit selection: -
Expert list: 1
Factory setting
0