Parameter
List of parameters
p0976
Reset and load all parameters / Reset load all par
CU_S110-CAN,
Can be changed: C1(30)
CU_S110-DP,
Data type: Unsigned16
CU_S110-PN
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
Resets or downloads all parameters of the drive system.
Value:
0:
1:
2:
3:
10:
11:
12:
20:
21:
22:
23:
24:
25:
26:
100:
1011: Start dnload of param. saved in volatile mem w/ p0977=1011
1012: Start dnload of param. saved in volatile mem w/ p0977=1012
1013: Start dnload of param. saved in volatile mem w/ p0977=1013
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
After all of the parameters have been reset to their factory setting, the system must be commissioned for the first
time again.
Resetting or loading is realized in the non-volatile memory.
Procedure:
1. Set p0009 = 30 (parameter reset).
2. Set p0976 to "required value". The system is rebooted.
p0976 is automatically set to 0 and p0009 is automatically set to 1 after this has been carried out.
p0977
Save all parameters / Save all par
CU_S110-CAN,
Can be changed: U, T
CU_S110-DP,
Data type: Unsigned16
CU_S110-PN
P-Group: Factory settings
Not for motor type: -
Min
0
Description:
Saves all parameters of the drive system to the non-volatile memory.
Value:
0:
1:
10:
11:
12:
20:
21:
22:
23:
24:
25:
26:
80:
1-184
Inactive
Start reset of all parameters to factory setting
Start dnload of param. saved in non-volatile mem w/ p0977=1
Start dnload of volatile parameters from RAM
Start dnload of param. saved in non-volatile mem w/ p0977=10
Start dnload of param. saved in non-volatile mem w/ p0977=11
Start dnload of param. saved in non-volatile mem w/ p0977=12
Start download Siemens internal setting 20
Start download Siemens internal setting 21
Start download Siemens internal setting 22
Start download Siemens internal setting 23
Start download Siemens internal setting 24
Start download Siemens internal setting 25
Start download Siemens internal setting 26
Start resetting of all BICO interconnections
Inactive
Save in non-volatile memory - downloaded at POWER ON
Save as opt. in non-vol. memory - downloaded w/ p0976=10
Save as opt. in non-vol. memory - downloaded w/ p0976=11
Save as opt. in non-vol. memory - downloaded w/ p0976=12
Save in non-volatile memory as setting 20 (reserved)
Save in non-volatile memory as setting 21 (reserved)
Save in non-volatile memory as setting 22 (reserved)
Save in non-volatile memory as setting 23 (reserved)
Save in non-volatile memory as setting 24 (reserved)
Save in non-volatile memory as setting 25 (reserved)
Save in non-volatile memory as setting 26 (reserved)
Save in non-volatile memory time-optimized (reserved)
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
1013
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
1013
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0