Missing enable signals
Missing enable signals that prevent the drive going into operation
(this situation can be detected at the ZSW sequence control, infeed r0899.2 = 1 [8926]).
Bit Nr.
Bedeutung
0
1 = OFF1, enable missing
1
1 = OFF2, enable missing
2
1 = OFF3, enable missing
3
1 = Enable operation missing
4
1 = Armature short-circuit/DC braking, enable missing
5
1 = STOP2, enable missing
6
1 = STOP1, enable missing
8
1 = EP terminals, enable missing
9
1 = Infeed, enable missing
10
1 = Ramp-function generator enable missing
11
1 = Ramp-function generator start missing
12
1 = Setpoint, enable missing
16
1 = OFF1, enable, internal missing
17
1 = OFF2, enable, internal missing
18
1 = OFF3, enable, internal missing
19
1 = Pulse enable, internal missing
20
1 = Internal armature short circuit/DC braking, enable missing
[2701.8]
21
1 = STOP2, enable internal missing
22
1 = STOP1, enable internal missing
25
1 = Function bypass active
26
1 = Drive inactive or not operational
27
Reserved
28
1 = Open brake missing
29
1 = Cooling system ready missing
30
1 = Speed controller inhibited
31
1 = Jog setpoint active
Logic operation
p2810[0]
(0)
AND operation
r2811.0
p2810[1]
(0)
1
2
DO: SERVO
Sequence control - Missing enable signals, line contactor control, logic operation
Line contactor control
Missing enable sig
r0046
r0046.0
[3020.5]
r0046.1
r0046.2
Fault with
r0046.3
OFF3 response
r0046.4
r0046.5
r0046.6
r0046.8
r0046.9
r0046.10
r0046.11
Line contactor control from sequence control
[2610.4]
r0046.12
r0046.16
r0046.17
r0046.18
r0046.19
r0046.20
r0046.21
r0046.22
r0046.25
r0046.26
r0046.28
r0046.29
r0046.30
r0046.31
p2816[0]
(0)
OR operation
r2817.0
p2816[1]
(0)
3
4
4000.00 μs
Control Unit
[3060.2]
0 = Internal fast stop
[3060.4]
1
[3070.2]
[3070.4]
1 = Internal RFG missing
[3060.2]
1
[3070.2]
Energize line contactor
DO
r0863.1
[2130]...[2133]
Line contactor feedback signal
p0860
DI
1
r0863.1
[2120]...[2133]
ON/OFF monitoring
p0861
F07300
T
0
"Line contactor
1
feedback signal
missing"
Time monitoring
Operating monitoring
&
&
5
6
fp_2634_98_eng.vsd
11.04.11 V04.04.00
From the line
supply
+24 V
To the infeed
7
8
Function diagram
- 2634 -
SINAMICS S110