Parameter
List of parameters
Dependency:
Refer to: p9560
Refer to: C01701
p9557
SI Motion pulse suppression test time (processor 1) / SI Mtn IL t_test
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [ms]
Description:
Sets the time after which the pulses must have been suppressed when initiating the test stop.
Dependency:
Refer to: C01798
Note:
A change only becomes effective after a POWER ON.
p9558
SI Motion acceptance test mode time limit (processor 1) / SI Mtn acc t P1
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
5000.00 [ms]
Description:
Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency:
Refer to: C01799
p9559
SI Motion forced checking procedure timer (processor 1) / SI Mtn dyn timer
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [h]
Description:
Sets the time interval for carrying out the forced checking procedure and testing the safety motion monitoring func-
tions integrated in the drives.
Within the parameterized time, the safety functions must have been tested at least once (including de-selection of
the "STO" function).
This monitoring time is reset each time the test is carried out.
The signal source to initiate the forced checking procedure is set in p9705.
Dependency:
Refer to: p9705
Refer to: A01697, C01798
Note:
STO: Safe Torque Off
p9560
SI Motion pulse suppression shutdown velocity (processor 1) / SI Mtn IL v_sh P1
SERVO_S110-CAN,
Can be changed: C2(95)
SERVO_S110-DP,
Data type: FloatingPoint32
SERVO_S110-PN
P-Group: Safety Integrated
Not for motor type: -
Min
0.00 [mm/min]
Description:
Sets the shutdown velocity for pulse suppression.
Below this velocity "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP
A).
In the case of encoderless motion monitoring functions, the parameter must be > 0 (recommended value: 10).
1-576
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
10000.00 [ms]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
100000.00 [ms]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
9000.00 [h]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
6000.00 [mm/min]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
100.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
40000.00 [ms]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
8.00 [h]
Access level: 3
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [mm/min]