Siemens SINAMICS S110 List Manual page 352

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

Parameter
List of parameters
p2289[0...n]
CI: Technology controller pre-control signal / Tec_ctrl prectrl
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: Unsigned32 / FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
-
Description:
Sets the signal source for the pre-control signal of the technology controller.
p2291
CO: Technology controller maximum limiting / Tec_ctrl max_limit
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
-200.00 [%]
Description:
Sets the maximum limit of the technology controller.
Dependency:
Refer to: p2292
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2292
CO: Technology controller minimum limiting / Tec_ctrl min_lim
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
-200.00 [%]
Description:
Sets the minimum limit of the technology controller.
Dependency:
Refer to: p2291
Caution:
The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2293
Technology controller ramp-up/ramp-down time / Tec_ctr ramp up/dn
SERVO_S110-CAN
Can be changed: U, T
(Tech_ctrl),
Data type: FloatingPoint32
SERVO_S110-DP
P-Group: Technology
(Tech_ctrl),
Not for motor type: -
SERVO_S110-PN
(Tech_ctrl)
Min
0.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
Refer to: p2291, p2292
Note:
The time refers to the set maximum and minimum limits (p2291, p2292).
1-352
Calculated: -
Dynamic index: CDS, p0170
Units group: -
Scaling: PERCENT
Max
-
Calculated: -
Dynamic index: -
Units group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dynamic index: -
Units group: -
Scaling: PERCENT
Max
200.00 [%]
Calculated: -
Dynamic index: -
Units group: -
Scaling: -
Max
100.00 [s]
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
100.00 [%]
Access level: 2
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
0.00 [%]
Access level: 3
Func. diagram: 7958
Unit selection: -
Expert list: 1
Factory setting
1.00 [s]